Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Manual Type |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
General
WSB1L series RCCB are suitable for distribution lines
with AC 50Hz, rated working voltage of AC240/400V and
rated current up to 63A and below. When the person gets
electric shock or the leakage current of the network exceeds
the specified value, the leakage circuit breakers can quickly
cut off the fault power supply in a very short time to protect
the safety of the person and the electrical equipment.
The RCCB have the advantages of advanced structure,
reliable performance and compact volume.The shell is made
of high impact resistance and flame retardant material.
The RCCB have the functions of overload, short circuit and
leakage protection. They are mainly used for overload, short
circuit and leakage protection of office buildings, residential
buildings and distiller buildings, distribution lines and
equipment. They can also be used for infrequent conversion
of lines under normal conditions.
Rated current | 16, 20, 25, 32, 40, 50, 63A |
Rated voltage Ue | AC240V (1P+N, 2P); AC400V (3P+N, 4P) |
Rated insulation voltage Ui | AC415 |
Rated impulse withstand voltage Uimp | 4kV |
Rated frequency | 50/60Hz |
Number of poles | 1P+N, 3P+N |
Module size | 36mm, 72mm |
Circuit type | AC type, A type, B type |
Breaking capacity | 6000A, 10000A |
Rated residual current I△n | 10mA, 30mA, 100mA, 300mA |
Rated residual operation current | 10, 30, 100, 300mA |
Optimum operation temperature | -5ºC to 40ºC |
Terminal tightening torque | 2.5-4N/m |
Terminal capacity (top) | 25mm² |
Terminal capacity (bottom) | 25mm² |
Electro-mechanical endurance | 4000 cycles |
Mounting | 35mm DIN rail |
The very new tripping structure makes more in safety | |
Suitable busbar | PIN busbar |
Standard | IEC61008-1 |