Serial Number | item | Unit | FKN12A-12D | FKRN12A-12D | ||
1 | Rated voltage | KV | 12 | 12 | ||
2 | Rated frequency | Hz | 50 | 50 | ||
3 | Rated current | A | 630 | 125 | ||
4 | Rated insulation level | 1min power frequency withstand voltage | To the ground, alternate | KV | 42 | 42 |
Isolation fracture | 48 | 48 | ||||
Lightning impulse withstand voltage (peak) | To the ground, alternate | 75 | 75 | |||
Isolation fracture | 85 | 85 | ||||
5 | Load switch | KA | 20 | - | ||
Ground switch | 20 | 20 | ||||
6 | Load switch | S | 4 | - | ||
Ground switch | 2 | 2 | ||||
7 | Rated short circuit closing current (peak) | KA | 50 | - | ||
8 | Rated breaking current | Active load breaking current | A | 630 | - | |
Closed-loop breaking current | 630 | - | ||||
5% active load breaking current | 31.5 | - | ||||
Cable charging current | 10 | - | ||||
Disconnect no-load transformer capacity | KVA | 1250 | 1250 | |||
9 | Rated short-circuit breaking current(current limiting fuse) | KA | - | 31.5 | ||
10 | Rated transfer current | A | - | 1200 | ||
11 | Mechanical life | Times | 2000 | 2000 | ||
12 | The kicker outputs power | J | - | 1+0.5 |